INT.P
Interface with potentiometer input
The P Interface turns the signal supplied by a potentiometric transducer into current 0-20 mA, 4-20 mA or voltage 0-10Vdc.
Its typical employment is the current or voltage transmission of signals supplied by a remote potentiometric transducer to remote supervision systems.
Special features of the P interface are its low cost and simple setting: activating two trimmers it’s possible to refer the entire output range to the stroke of the poten-tiometer effectivly employed.
The instrument is carried out in a 3-module case for assembling on DIN EN50022 guide.
VERSIONS
VERSIONS | |
INTP0 | Power supply 115Vac |
INTP1 | Power supply 230Vac |
INTP2 | Power supply 24Vac |
INTP3 | Power supply 24Vdc |
TECHNICAL FEATURES | |
Input impedance | 1 Mohm |
Linearity | endless |
Max. load impedance for current output | 600 Ohm |
Min. load impedance for voltage output | 1Kohm |
Output resolution | 12 Bit |
Outputs | 0÷10 Vdc; 4÷20mA; 0÷20mA |
Potentiometer input | 1÷50 Kohm |
Power supply | 115Vac, 230Vac, 24Vac, 24Vdc 3VA |
Relative humidity | 10 ÷ 90 % |
Working temperature | ÷50°C |
EMC | 2014/30/UE |
RoHS |
2011/65/UE |
DIMENSIONS |
![]() |
INTP0 | Power supply 115Vac |
INTP1 | Power supply 230Vac |
INTP2 | Power supply 24Vac |
INTP3 | Power supply 115Vdc |
Richiedi l'accesso
Int_P_R4_ing.pdf
Click here to download >